14/4/2026

Risk Mechanisms, Verification Approaches, and the Importance of ASTM E2336 and UL 2221

Commercial kitchens are among the most challenging areas in a building from a fire-risk perspective due to high heat input, frequent ignition sources, and the continuous generation of grease vapours. Although the fire often starts at cooking equipment, the critical factor that shapes the consequences is frequently what happens along the kitchen exhaust route. Grease exhaust duct (kitchen exhaust duct) systems can accumulate combustible grease deposits over time; they may also run long distances and often pass through shafts or multi-storey routes. Therefore, duct runs that are not designed, protected, and maintained with a system approach can unintentionally become a “transfer path” that carries fire and heat beyond the kitchen compartment.

In projects where fire resistance is required, fire-resistive insulation solutions are preferred along the grease exhaust duct route. However, the reliability of these solutions—especially at penetrations, hanger/support details, and service access points—must be demonstrated through testing. ASTM E2336 and UL 2221 are two commonly used reference standards for evaluating the performance of grease exhaust duct systems under specified fire exposures.


Grease exhaust duct: A fire pathway that amplifies consequences

Two fire scenarios are decisive in grease exhaust duct engineering:

In both scenarios, the objective is the same: to preserve compartmentation and prevent the fire from spreading to a remote location away from the kitchen. Because the duct route includes elbows, joints, service access points, and transitions (penetrations), real performance is determined not by a single material property but by the system’s holistic in-service behaviour. Testing the system as an assembly—including all installation components—is therefore a critical parameter for demonstrating how closely the on-site installation matches the tested/verified configuration.


ASTM E2336 and UL 2221: System-Based Verification of Grease Exhaust Duct Fire Performance

ASTM E2336 and UL 2221 serve essentially the same purpose in practice. They verify the performance of all materials used for grease exhaust ducts as a system/assembly. The assessment does not focus only on the material; joints, hanger/supports, connections, and penetration details are also considered part of the system.

In both standards, the fundamental fire scenarios are similar. The first is the internal duct fire (grease fire) scenario. The second is the external fire exposure scenario (external influence from spaces such as shafts or suspended ceilings). After the fire exposure, the “hose stream” step is used to challenge the system integrity and the robustness of critical details.

On the material side, noncombustibility/combustibility expectations are addressed within a common framework. Typically, noncombustibility in accordance with ASTM E136 is required. In addition, flame spread and smoke development are limited based on ASTM E84 / UL 723.

Scope of Fire Resistance Tests:
The tests are carried out on a grease exhaust duct specimen protected with insulation material. The specimen is prepared to represent field application, and the installation is performed in accordance with the manufacturer/sponsor’s instructions. The report also defines critical details such as the support/hanger system and (if applicable) access/cleaning doors. The external fire test setup simulates the duct passing through a floor slab from inside the furnace and exiting to the outside.

Thermal exposure (internal fire):
In the internal fire test, the duct internal temperature is increased in a controlled manner using gas burners in the test furnace. The internal temperature is increased to at least 500°F (260°C) within 15 minutes and maintained at this level for at least 4 hours. Subsequently, within 15 minutes after the end of the 4-hour period, the internal temperature is increased to at least 2000°F (1093°C) and maintained for 30 minutes.

Measurements and acceptance criteria:
Four thermocouples are used inside the duct for measuring the internal temperature. Temperature increase on the external (unexposed) surface is monitored using at least 16 surface thermocouples placed at locations representing the most adverse heat transmission (including surfaces, joints, support/hanger contact points, and around the access door).

Acceptance criteria are based on limits such as: during the 500°F phase, the temperature rise at any external surface thermocouple shall not exceed 117°F (65°C); during the 2000°F phase, the average temperature rise of external surface thermocouples shall not exceed 250°F (139°C), and no individual thermocouple shall exceed 325°F (181°C). In addition, integrity criteria are evaluated, including the external insulation system remaining in place, no openings/voids forming, and no sustained flaming on the unexposed side (except for limited exceptions defined in the standard).

The external fire test is applied to a separate duct specimen. In this stage, the setup is tested in a horizontal furnace in accordance with the ASTM E119 time–temperature curve for the duration specified by the sponsor; measurement and evaluation are carried out on the basis of ASTM E119 and ASTM E814, and the specimen is subsequently subjected to a hose stream. At this stage, no openings shall form in the duct, and the firestop at the floor penetration is expected to meet the ASTM E814 F-rating requirements (and T-rating requirements for horizontal penetrations).


Critical Details That Determine On-Site Performance

Performance losses in real installations often occur at the same points. For this reason, a technical design review should focus in particular on the following topics:

These topics are not “secondary”; in many projects they are the primary factors that determine performance, because complexity and field variability accumulate most in these details.


What Critical Details Should a Good Test Report Include?

For design teams, investors, and authorities, a “usable” test report does not only present the name of a standard and a table of results. It must clearly describe what the tested system is made of, under which conditions it was verified, and which details must be adhered to in field of application. At a minimum, the following elements should be presented clearly and traceably:

A report that is clear at this level and that specifies boundaries will reduce the design uncertainty. It also prevents installation teams from changing critical details based on “similar application” assumptions and reduces the risk of last-minute revisions on site.


The Bridge Between Expertise and Correct Application

Grease exhaust duct fire safety lies at the intersection of fire testing, buildable detail design, and operational realities. The most reliable outcomes are achieved by teams that treat the duct route as a system, translate test evidence correctly to the field, and maintain installation/operational discipline.

Efectis ensures that project-critical technical aspects are evaluated within test-based verification activities, and that the findings are translated into documentation aligned with the project’s objectives.